APPA 33II Manuale delle Istruzioni Pagina 9

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 16
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 8
8
(2) AC Current : Auto-ranging
Range Resolution Accuracy
Overload
protection
200A 0.1A ±(1.9%rdg + 5dgt) 50/60Hz
600A 1A
±(1.5%rdg + 5dgt) 50/60Hz (for 0 ~ 400A)
±(2.5%rdg + 5dgt) 50/60Hz (for 400 ~ 600A)
800A
* AC Conversion Type : Average Sensing rms indication. (33)
AC Conversions are ac-coupled, true rms responding , calibrated to the rms value
since wave input , the basic accuracy is for sine wave at full scale, for non-sine wave
accuracy reference to ** (33R)
** Crest Factor : 2 to 3 , add 1.4% to Accuracy.
3 to 4 , add 3% to Accuracy.
Vedere la pagina 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Commenti su questo manuale

Nessun commento